Programming Guide | VLT® AutomationDrive FC 360
14-30 Current Lim Ctrl, Proportional Gain
Default value:
100%
Setup:
All setups
Data type:
Uint16
Enter the proportional gain value for the current limit controller. Selection of a high value makes the controller react faster. Too high a
setting leads to controller instability.
14-31 Current Lim Ctrl, Integration Time
Default value:
Size related
Setup:
All setups
Data type:
Uint16
Control the current limit control integration time. Setting it to a lower value makes it react faster. A setting too low leads to control
instability.
14-32 Current Lim Ctrl, Filter Time
Default value:
5.0 ms
Setup:
All setups
Data type:
Uint16
Set a time constant for the current limit controller low-pass filter.
14-34 Stall Protection Adjustment Factor
Default value:
100%
Setup:
All setups
Data type:
Uint8
Define the stall protection adjustment factor.
14-35 Stall Protection
Default value:
[1] Enabled
Setup:
All setups
Data type:
Uint8
Enable or disable the stall protection function.
Option
[0]
[1]
240
| Danfoss A/S © 2024.01
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Name
Disabled
Enabled
Range (0–500%)
0
True
Range (0.002–2 s)
-3
True
Range (1.0–100.0 ms)
-1
True
Range (50%–200%)
0
True
Option
False
Description
Disable the stall protection function.
Enable the stall protection when field
weakening mode and Flux mode are
active.
AU275649936274en-001401 / 130R0507