Programming Guide | VLT® AutomationDrive FC 360
33-02 Home Ramp Time
Default value:
1000 ms
Setup:
1 setup
Data type:
Uint16
This parameter defines the ramp time (in ms) from standstill to the value set in parameter 32-80 Maximum Allowed Velocity.
33-03 Homing Velocity
Default value:
100 RPM
Setup:
1 setup
Data type:
Int16
This parameter defines the velocity of homing. It must not exceed the parameter 32-80 Maximum Allowed Velocity.
33-04 Homing Behavior
Default value:
[1] Reverse no index
Setup:
1 setup
Data type:
Uint8
Define the behavior when the home switch is found: Reversing without index (0 pulse) search, or forwarding without index search.
Option
[1]
[3]
33-4* Limit Handling
4.22.2
33-41 Negative Software Limit
Default value:
-500000
Setup:
1 setup
Data type:
Int32
This parameter is active only during positioning if parameter 33-43 Negative Software Limit Active is set to [1] Active. When parameter
34-50 Actual Position reaches below the negative software limit set in this parameter, a position control fault alarm is reported.
33-42 Positive Software Limit
Default value:
500000
Setup:
1 setup
Data type:
Int32
Danfoss A/S © 2024.01
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Name
Reverse no index
Forward no index
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
AU275649936274en-001401 / 130R0507 |
Range (50–5000 ms)
0
True
Range (-1500–1500 RPM)
0
True
Option
–
True
Range (-1073741824–
1073741824)
0
True
Range (-1073741824–
1073741824)
0
True
287