Programming Guide | VLT® AutomationDrive FC 360
4-2* Limit Factors
4.5.2
4-20 Torque Limit Factor Source
Default value:
[0] No function
Setup:
All setups
Data type:
Uint8
Select an analog input for scaling the settings in parameter 4-16 Torque Limit Motor Mode and parameter 4-17 Torque Limit Generator
Mode 0–100% (or inverse). The signal levels corresponding to 0% and 100% are defined in the analog input scaling, for example
parameter group 6-1* Analog Input 1. This parameter is only active when parameter 1-00 Configuration Mode is set to [0] Open Loop or
[1] Speed Closed Loop.
Option
[0]
[2]
[4]
[6]
[8]
[18]
4-21 Speed Limit Factor Source
Default value:
[0] No function
Setup:
All setups
Data type:
Uint8
Select an analog input for scaling the settings in parameter 4-19 Max Output Frequency 0–100% (or inverse). The signal levels
corresponding to 0% and 100% are defined in the analog input scaling, for example parameter group 6-1* Analog Input 1. This
parameter is only active when parameter 1-00 Configuration Mode is in torque mode.
Option
[0]
[2]
[4]
[6]
[8]
[18]
4-22 Break Away Boost
Default value:
[0] Off
Danfoss A/S © 2024.01
Parameter type:
Conversion index:
Change during operation:
Name
No function
Analog in 53
Analog in 53 inv
Analog in 54
Analog in 54 inv
Bus Control
Parameter type:
Conversion index:
Change during operation:
Name
No function
Analog in 53
Analog in 53 inv
Analog in 54
Analog in 54 inv
Bus Control
Parameter type:
AU275649936274en-001401 / 130R0507 |
Option
–
True
Option
–
True
Option
101