Programming Guide | VLT® AutomationDrive FC 360
1-22 Motor Voltage
Default value:
Size related
Setup:
All setups
Data type:
Uint16
Enter the nominal motor voltage according to the motor nameplate data. The default value corresponds to the nominal rated output of
the unit.
1-23 Motor Frequency
Default value:
Size related
Setup:
All setups
Data type:
Uint16
Select the motor frequency value from the motor nameplate. For 87 Hz operation with 230/440 V motors, set the value according to the
nameplate data for 230 V/50 Hz. Adapt parameter 4-14 Motor Speed High Limit [Hz] and parameter 3-03 Maximum Reference to the 87
Hz application.
1-24 Motor Current
Default value:
Size related
Setup:
All setups
Data type:
Uint32
Enter the nominal motor current value from the motor nameplate data. This data is used for calculating motor torque, motor thermal
protection, and so on.
1-25 Motor Nominal Speed
Default value:
Size related
Setup:
All setups
Data type:
Uint16
Enter the nominal motor speed value from the motor nameplate data. This data is used for calculating automatic motor compensations.
1-26 Motor Cont. Rated Torque
Default value:
Size related
Setup:
All setups
Data type:
Uint32
Enter the value from the motor nameplate data. The default value corresponds to the nominal rated output. This parameter is available
when parameter 1-10 Motor Construction is set to [1] PM, non salient SPM or [3] PM, salient IPM, that is, the parameter is valid for PM,
non-salient SPM and PM, salient IPM motors only.
1-29 Automatic Motor Adaption (AMA)
Default value:
[0] Off
Danfoss A/S © 2024.01
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Parameter type:
AU275649936274en-001401 / 130R0507 |
Range (50–1000 V)
0
False
Range (5–500 Hz)
0
False
Range (0.01–1000.00 A)
-2
False
Range (50–60000 RPM)
0
False
Range (0.1–10000.0 Nm)
-1
False
Option
59