Programming Guide | VLT® AutomationDrive FC 360
Enter the filter time constant. This is a first-order digital lowpass filter time constant for suppressing electrical noise in terminal X48/10. A
high time constant value improves dampening but also increases the time delay through the filter.
35-35 Term. X48/10 Temp. Monitor
Default value:
[0] Disabled
Setup:
All setups
Data type:
Uint8
This parameter gives the possibility of enabling or disabling the temperature monitor for terminal X48/10. The temperature limits can be
set in parameter 35-36 Term. X48/10 Low Temp. Limit/parameter 35-37 Term. X48/10 High Temp. Limit.
Option
[0]
[1]
35-36 Term. X48/10 Low Temp. Limit
Default value:
-50
Setup:
All setups
Data type:
Int16
Enter the minimum temperature reading that is expected for normal operation of the temperature sensor at terminal X48/10.
35-37 Term. X48/10 High Temp. Limit
Default value:
204
Setup:
All setups
Data type:
Int16
Enter the maximum temperature reading that is expected for normal operation of the temperature sensor at terminal X48/10.
Parameter Group 37-** Application Settings
4.25
37-0* Application Mode
4.25.1
37-00 Application Mode
Default value:
[0] Drive mode
Setup:
All setups
Data type:
Uint8
Set the application mode.
Danfoss A/S © 2024.01
Parameter type:
Conversion index:
Change during operation:
Name
Disabled
Enabled
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
AU275649936274en-001401 / 130R0507 |
Option
–
True
Range (-50–204)
0
True
Range (-50–204)
0
True
Option
–
False
297