Use this parameter to set the inductance saturation point.
1-49 Current at Min Inductance for q-axis
Default value:
100%
Setup:
All setups
Data type:
Uint16
This parameter specifies the saturation curve of the q-inductance values. From 20–100% of this parameter, the inductance is linearly
approximated due to parameter 1-38 q-axis Inductance (Lq) and parameter 1-45 q-axis Inductance Sat. (LqSat). These parameters are
related to the motor nameplate load compensations, the application load type, and the electronic brake function for quick stop/hold of
the motor.
1-5* Load Indep. Setting
4.2.6
Parameters for load-independent motor settings.
1-50 Motor Magnetisation at Zero Speed
Default value:
100%
Setup:
All setups
Data type:
Uint16
Use this parameter along with parameter 1-52 Min Speed Normal Magnetising [Hz] to obtain a different thermal load on the motor when
running at low speed. Enter a value that is a percentage of the rated magnetizing current. If the setting is too low, the torque on the
motor shaft may be reduced.
Magn. current
90%
Par. 1-50
Par. 1-52
Figure 16: Motor Magnetization
1-52 Min Speed Normal Magnetising [Hz]
Default value:
1.0 Hz
Setup:
All setups
Data type:
Uint16
Set the required frequency for normal magnetizing current. Use this parameter along with parameter 1-50 Motor Magnetisation at Zero
Speed.
1-53 Model Shift Frequency
Default value:
Size related
Setup:
All setups
Data type:
Uint16
Danfoss A/S © 2024.01
Hz
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
AU275649936274en-001401 / 130R0507 |
Range (20–200%)
0
False
Range (0–300%)
0
True
Range (0.1–10.0 Hz)
-1
True
Range (4.0–65535.0 Hz)
-1
False
65