Programming Guide | VLT® AutomationDrive FC 360
Data type:
Uint8
Enable or disable the advanced cable diagnosis function. If enabled, the distance to cable errors can be read out in parameter 12-93
Cable Error Length. The parameter resumes to the default setting [0] Disabled after the diagnostics have finished.
The cable diagnostics function is only issued on ports where there is no link (see parameter 12-10 Link Status).
Option
[0]
[1]
12-91 Auto Cross Over
Default value:
[1] Enabled
Setup:
1 setup
Data type:
Uint8
Enable or disable the auto-crossover function.
Disabling of the auto-crossover function requires crossed Ethernet cables for daisy chaining the options.
Option
[0]
[1]
12-92 IGMP Snooping
Default value:
[1] Enabled
Setup:
1 setup
Data type:
Uint8
Enable or disable the IGMP Snooping function. This avoids flooding of the Ethernet protocol stack by only forwarding multicast packets
to ports that are a member of the multicast group.
Option
[0]
[1]
208