13-03 Reset SLC
Default value:
[0] Do not reset SLC
Setup:
1 setup
Data type:
Uint8
Reset all parameters in parameter group 13-** Smart Logic to default settings.
Option
[0]
[1]
13-1* Comparators
4.12.3
Comparators are used for comparing continuous variables (that is output frequency, output current, analog input, and so on.) to fixed
preset values.
Par. 13-10
Comparator Operand
Par. 13-12
Comparator Value
Figure 41: Comparators
There are digital values that are compared to fixed time values. See explanation in parameter 13-10 Comparator Operand. Comparators
are evaluated once in each scan interval. Use the result (true or false) directly. All parameters in this parameter group are array
parameters with index 0 to 5. Select index 0 to program comparator 0, select index 1 to program comparator 1, and so on.
Danfoss A/S © 2024.01
Name
Do not reset SLC
Reset SLC
Par. 13-11
Comparator Operator
=
TRUE longer than.
. . .
. . .
Comparator 5
Logic rule 4
Logic rule 5
SL Time-out 3
SL Time-out 4
SL Time-out 5
SL Time-out 6
SL Time-out 7
Broken Belt
Parameter type:
Conversion index:
Change during operation:
Description
Do not reset the parameters in parameter
group 13-** Smart Logic.
Reset all parameters in parameter group
13-** Smart Logic to default settings.
AU275649936274en-001401 / 130R0507 |
Option
True
215