Programming Guide | VLT® AutomationDrive FC 360
Option
[13]
[14]
[15]
[16]
[17]
[18]
[19]
[20]
[21]
[22]
[23]
[24]
[25]
[26]
[27]
Danfoss A/S © 2024.01
Name
Below current, low
Above current, high
Out of frequency range
Below frequency, low
Above frequency, high
Out of feedb. range
Below feedback, low
Above feedback, high
Thermal warning
Ready, no thermal warning
Remote, ready, no TW
Ready, no over-/under voltage
Reverse
Bus OK
Torque limit & stop
Description
The motor current is lower than set in
parameter 4-50 Warning Current Low.
The motor current is higher than set in
parameter 4-51 Warning Current High.
Output frequency is outside the frequency
range.
The output speed is lower than the setting
in parameter 4-40 Warning Freq. Low.
The output speed is higher than the
setting in parameter 4-41 Warning Freq.
High.
The feedback is outside the range set in
parameter 4-56 Warning Feedback Low
and parameter 4-57 Warning Feedback
High.
The feedback is below the limit set in
parameter 4-56 Warning Feedback Low.
The feedback is above the limit set in
parameter 4-57 Warning Feedback High.
The thermal warning turns on when the
temperature exceeds the limit in the
motor, the drive, the brake resistor, or the
thermistor.
The drive is ready for operation, and there
is no overtemperature warning.
The drive is ready for operation
and is in auto-on mode. There is no
overtemperature warning.
The drive is ready for operation and the
mains voltage is within the specified
voltage range (see Specifications section
in the design guide).
The motor runs (or is ready to
run) clockwise when logic = 0 and
counterclockwise when logic = 1. The
output changes when the reversing signal
is applied.
Active communication (no timeout) via
the serial communication port.
Use in performing a coast stop and in
torque limit condition. If the drive has
received a stop signal and is at the torque
limit, the signal is logic 0.
AU275649936274en-001401 / 130R0507 |
131
Need help?
Do you have a question about the VLT AutomationDrive FC 360 and is the answer not in the manual?
Questions and answers