Programming Guide | VLT® AutomationDrive FC 360
6-25 Terminal 54 High Ref./Feedb. Value
Default value:
Size related
Setup:
All setups
Data type:
Int32
Enter the reference or feedback value that corresponds to the voltage or current set in parameter 6-21 Terminal 54 High
Voltage/parameter 6-23 Terminal 54 High Current.
6-26 Terminal 54 Filter Time Constant
Default value:
0.01 s
Setup:
All setups
Data type:
Uint16
Enter the time constant, which is a first order digital low-pass filter time constant for suppressing electrical noise in terminal 54. A high
time constant value improves dampening, but also increases the time delay through the filter.
6-29 Terminal 54 mode
Default value:
[1] Voltage mode
Setup:
1 setup
Data type:
Uint8
Select if terminal 54 is used for current input or voltage input.
Option
[0]
[1]
6-7* Analog/Digital Output 45
4.7.5
Parameters for configuring the scaling and limits for analog/digital output terminal 45. Analog outputs are current outputs: 0/4–20 mA.
Resolution on analog output is 12 bit. Analog output terminals can also be set up as digital output.
6-70 Terminal 45 Mode
Default value:
[0] 0-20 mA
Setup:
All setups
Data type:
Uint8
Set terminal 45 to act as analog output or as digital output.
148
| Danfoss A/S © 2024.01
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Name
Current mode
Voltage mode
Parameter type:
Conversion index:
Change during operation:
Range (-4999.000–4999.000)
-3
True
Range (0.01–10.00 s)
-2
True
Option
True
Option
True