Programming Guide | VLT® AutomationDrive FC 360
Select the input to which the thermistor (PTC sensor) should be connected. If an analog input in this parameter is set as a source, it
cannot be used for another purpose, for example, reference or feedback.
Digital input should be set to [0] PNP - Active at 24 V in parameter 5-00 Digital Input Mode.
Option
[0]
[1]
[2]
[3]
[4]
[5]
[6]
[7]
Parameter Group 2-** Brakes
4.3
2-0* DC-Brake
4.3.1
Use this parameter group to configure DC brake and DC hold functions.
2-00 DC Hold/Motor Preheat Current
Default value:
50%
Setup:
All setups
Data type:
Uint16
Set the holding current as a percentage of the rated motor current I
function (holding torque) or pre-heats the motor. This parameter is active if [0] DC hold is selected in parameter 1-72 Start Function, or if
[1] DC hold/preheatis selected in parameter 1-80 Function at Stop.
The maximum value depends on the rated motor current. Avoid 100% current for too long. It may damage the motor.
2-01 DC Brake Current
Default value:
50%
Setup:
All setups
Data type:
Uint16
78
| Danfoss A/S © 2024.01
  NOTICE
Name
None
Analog Input 53
Analog Input 54
Digital input 18
Digital input 19
Digital input 32
Digital input 33
Digital input 31
Parameter type:
Conversion index:
Change during operation:
parameter 1-24 Motor Current. This parameter holds the motor
M,N
  NOTICE
Parameter type:
Conversion index:
Change during operation:
Range (0–160%)
0
True
Range (0–150%)
0
True
AU275649936274en-001401 / 130R0507