Programming Guide | VLT® AutomationDrive FC 360
Data type:
Uint16
Use this parameter for setting a higher limit for the frequency range. When the motor speed exceeds this limit, the display reads Speed
high. Warning bit 9 is set in parameter 16-94 Ext. Status Word. Output relay can be configured to indicate this warning. LCP warning
indicator light is not lit when the limit set is reached. The value must exceed the value in parameter 4-40 Warning Freq. Low and must
not exceed the value in parameter 4-14 Motor Speed High Limit [Hz].
4-42 Adjustable Temperature Warning
Default value:
0
Setup:
All setups
Data type:
Uint8
Use this parameter to set the motor temperature limit.
4-43 Motor Speed Monitor Function
Default value:
[0] Disabled
Setup:
All setups
Data type:
Uint8
Select how the drive should react when too high speed is detected, that is, when the motor speed signal is higher that the reference
after the speed ramp with more than specified in parameter 4-44 Motor Speed Monitor Max during the time set in parameter 4-45 Motor
Speed Monitor Timeout.
Option
[0]
[1]
[2]
[12]
[13]
4-44 Motor Speed Monitor Max
Default value:
300 RPM
Setup:
All setups
Data type:
Uint16
Enter the maximum allowed speed between the reference after the ramp and the actual mechanical shaft speed.
4-45 Motor Speed Monitor Timeout
Default value:
0.10 s
Setup:
All setups
Data type:
Uint16
Danfoss A/S © 2024.01
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Name
Disabled
Warning
Trip
Trip/Warning
Trip/Catch
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
AU275649936274en-001401 / 130R0507 |
True
Range (0–200)
0
True
Option
True
Range (10–500 RPM)
0
True
Range (0.00 s–60.00 s)
-2
True