Programming Guide | VLT® AutomationDrive FC 360
Table 27: Description of Warning Word
Bit
Hex
Dec
Warning Word
0
00000001
1
1
00000002
2
2
00000004
4
3
00000008
8
4
00000010
16
5
00000020
32
6
00000040
64
7
00000080
128
8
00000100
256
9
00000200
512
10
00000400
1024
11
00000800
2048
12
00001000
4096
13
00002000
8192
14
00004000
16384
15
00008000
32768
16
00010000
65536
17
00020000
131072
18
00040000
262144
19
00080000
524288
20
00100000
1048576
21
00200000
2097152
22
00400000
4194304
23
00800000
8388608
24
01000000
16777216
25
02000000
33554432
26
04000000
67108864
27
08000000
134217728
28
10000000
268435456
Danfoss A/S © 2024.01
Warning word
Parameter 16-92 Warning
Word
Brake check (W28)
Pwr.card temp (A69)
Earth fault (W14)
Ctrl.card temp (W65)
Ctrl. word TO (W17)
Overcurrent (W13)
Torque limit (W12)
Motor th over (W11)
Motor ETR over (W10)
Inverter Overld (W9)
DC under volt (W8)
DC over volt (W7)
–
–
Mains ph. loss (W4)
No motor (W3)
Live zero error (W2)
–
Brake overload (W26)
Brake resistor (W25)
Brake IGBT (W27)
Speed limit (W49)
Fieldbus fault (W34)
24 V supply low (W47)
Mains failure (W36)
Current limit (W59)
Low temp (W66)
Voltage limit (W64)
Encoder loss (W90)
Warning word 2
Parameter 16-93 Warning
Word 2
Start delayed
Stop delayed
–
–
Check Valve Failure
–
–
–
Broken Belt
–
–
–
–
–
Safe option warning
Auto DC braking
–
Fans warn
–
T27 overload
T29 overload
Memory Module
–
–
Power Limit Motor
Power Limit Generator
–
Feedback fault
AU275649936274en-001401 / 130R0507 |
Warning word 3
Parameter 16-98 Warning
Word 3
–
–
–
–
–
Speed monitor
Profibus converter time
warning
User Alert Warning
–
–
Hoist Mech Brake
Temp Input Error
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
311