Page 11
The operating guide provides basic information on mechanical dimensions, installation, and programming. The design guide provides information on how to design motor control systems. Supplementary publications and manuals are available from the Danfoss website. Document and Software Version This guide is regularly reviewed and updated. All suggestions for improvement are welcome.
Page 18
Programming Guide | VLT® AutomationDrive FC 360 Safety Safety Symbols The following symbols are used in Danfoss documentation. DANGER Indicates a hazardous situation which, if not avoided, will result in death or serious injury. WARNING Indicates a hazardous situation which, if not avoided, could result in death or serious injury.
Page 21
Programming Guide | VLT® AutomationDrive FC 360 NOTICE HIGH ALTITUDES For installation at altitudes above 2000 m (6562 ft), contact Danfoss regarding PELV. NOTICE USE ON ISOLATED MAINS For details about the use of the drive on isolated mains, refer to the section RFI Switch in the design guide. Follow the recommendations regarding the installation on IT mains.
Page 22
LCP 21 and LCP 23. The drive can also be programmed from the VLT® Motion Control Tool MCT 10 on PC via RS485 com-port. This software can be ordered using code number 130B1000 or downloaded from the Danfoss website: https://www.danfoss.com/en/service-and-support/downloads/ dds/vlt-motion-control-tool-mct-10/#tab-overview.
Page 311
– – These faults may be caused by mains distortions. Installing a Danfoss line filter may rectify this problem. For enclosure size J7, the warning can also be caused by high UDC voltage. Alarm Word, Warning Word, and Extended Status Word 5.1.6...
Page 322
Power cycle the drive. If the alarm occurs again, contact a Dan- foss supplier. Troubleshooting See the above table for the causes and solutions for different internal faults. If the fault persists, contact the Danfoss supplier or service department for assistance. WARNING 40, Overload T27 Troubleshooting Check the load connected to terminal 27 or remove the short-circuit connection.
Page 323
ALARM 50, AMA Calibration Cause A calibration error has occurred. Troubleshooting Contact a Danfoss supplier or the Danfoss service department. ALARM 51, AMA check U and I Cause The settings for motor voltage, motor current, and motor power are wrong.
Page 324
Try to restart the AMA. Repeated restarts can overheat the motor. ALARM 58, AMA Internal Fault Cause An AMA internal fault occurs. Troubleshooting Contact a local Danfoss supplier. WARNING/ALARM 59, Current Limit Cause The current is higher than the value in parameter 4-18 Current Limit. Troubleshooting Ensure that the motor data in parameter 1-20 to parameter 1-25 is set correctly.
Page 326
Cause The control card and power card are incompatible. Troubleshooting To check compatibility, contact the Danfoss supplier with the type code from the unit nameplate and the part numbers on the cards. ALARM 80, Drive Initialized to Default Value Cause Parameter settings are initialized to default settings after a manual reset.
Page 331
Residual current device Regen Regenerative terminals Radio frequency interference Minimum allowed brake resistor value by the drive Root average square Revolutions per minute Recommended brake resistor resistance of Danfoss brake resistors Stator resistance Second Silicon controlled rectifier SCCR Short-circuit current rating SFAVM...
Page 340
Danfoss reserves the right to alter its products without notice. This also applies to products ordered but not delivered provided that such alterations can be made without changes to form, fit or function of the product. All trademarks in this material are property of Danfoss A/S or Danfoss group companies.