Programming Guide | VLT® AutomationDrive FC 360
Option
[0]
[1]
[2]
[3]
[4]
[5]
[6]
[7]
[8]
[9]
[10]
[11]
[12]
[13]
[14]
[15]
[16]
150
| Danfoss A/S © 2024.01
Name
No operation
Control Ready
Drive ready
Drive rdy/rem ctrl
Stand-by/no warning
Running
Running/no warning
Run in range/no warn
Run on ref/no warn
Alarm
Alarm or warning
At torque limit
Out of current range
Below current, low
Above current, high
Out of frequency range
Below frequency, low
Description
Default for all digital outputs and relay
outputs.
The control card is ready.
The drive is ready for operation and
applies a supply signal on the control
board.
The drive is ready for operation and is in
auto-on mode.
Ready for operation. No start or stop
command is given (start/disable). No
warnings are active.
The motor is running and shaft torque is
present.
The motor is running and there are no
warnings.
The motor is running within the
programmed current and speed ranges
set in parameter 4-50 Warning Current
Low to parameter 4-51 Warning Current
High. There are no warnings.
The motor runs at reference speed. No
warnings.
An alarm activates the output.
An alarm or a warning activates the
output.
The torque limit set in parameter 4-16
Torque Limit Motor Mode or parameter
4-17 Torque Limit Generator Mode has
been exceeded.
The motor current is outside the range set
in parameter 4-18 Current Limit.
The motor current is lower than set in
parameter 4-50 Warning Current Low.
The motor current is higher than set in
parameter 4-51 Warning Current High.
Output frequency is outside the frequency
range.
The output speed is lower than the setting
in parameter 4-40 Warning Freq. Low.
AU275649936274en-001401 / 130R0507