Programming Guide | VLT® AutomationDrive FC 360
Option
[3]
[4]
[5]
[6]
1-73 Flying Start
Default value:
[0] Disabled
Setup:
All setups
Data type:
Uint8
Catch a motor which is spinning freely due to a mains dropout.
To obtain the best flying start performance, the advanced motor data, parameter 1-30 Stator Resistance (Rs) to parameter 1-35
Main Reactance (Xh), must be correct.
Danfoss A/S © 2024.01
Name
Start speed cw
Horizontal operation
VVC+ clockwise
Hoist Mech. Brake Rel
Parameter type:
Conversion index:
Change during operation:
  NOTICE
Description
Only possible with VVC+. Regardless of
the value applied by the reference signal,
the output speed applies the setting
of the start speed in parameter 1-75
Start Speed [Hz] and the output current
corresponds to the setting of the start
current in parameter 1-76 Start Current.
This function is typically used in hoisting
applications without counterweight
and especially in applications with a
Cone motor, where the start is clockwise,
followed by rotation in the reference
direction.
Only possible with VVC+. For obtaining
the function described in parameter
1-75 Start Speed [Hz] and parameter
1-76 Start Current during the start delay
time. The motor rotates in the reference
direction. If the reference signal equals
zero (0), parameter 1-75 Start Speed [Hz] is
ignored, and the output speed equals zero
(0). The output current corresponds to the
setting of the start current in parameter
1-76 Start Current.
The start speed is calculated
automatically. This function uses the start
speed in the start delay time only.
For Hoist function, select this option
during start delay.
Option
True
AU275649936274en-001401 / 130R0507 |
71