Programming Guide | VLT® AutomationDrive FC 360
4-27 Torque Limit Bus Control
Default value:
0
Setup:
All setups
Data type:
Uint16
This parameter is used to specify the bus factor to control the torque limit. It only works when parameter 4-20 Torque Limit Factor Source
is set to [18] Bus Control.
4-28 Speed Limit Bus Control
Default value:
0
Setup:
All setups
Data type:
Uint16
This parameter is used to specify the bus factor to control the speed limit. It only works when parameter 4-21 Speed Limit Factor Source
is set to [18] Bus Control.
4-3* Motor Fb Monitor
4.5.3
4-30 Motor Feedback Loss Function
Default value:
[2] Trip
Setup:
All setups
Data type:
Uint8
This function is used to monitor consistency in the feedback signal if the feedback signal is available. Select the action of the drive if a
feedback fault is detected. The selected action takes place when the feedback signal differs from the output speed by the value set in
parameter 4-31 Motor Feedback Speed Error for longer than the value set in parameter 4-32 Motor Feedback Loss Timeout.
Option
[0]
[1]
[2]
[3]
[4]
[5]
[6]
4-31 Motor Feedback Speed Error
Default value:
20 Hz
Setup:
All setups
Data type:
Uint16
Danfoss A/S © 2024.01
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Name
Disabled
Warning
Trip
Jog
Freeze Output
Max Speed
Switch to Open Loop
Parameter type:
Conversion index:
Change during operation:
AU275649936274en-001401 / 130R0507 |
Range (0–16384)
0
True
Range (0–16384)
0
True
Option
True
Range (0–50 Hz)
0
True