Programming Guide | VLT® AutomationDrive FC 360
6-13 Terminal 53 High Current
Default value:
20.00 mA
Setup:
All setups
Data type:
Uint16
Enter the high current value corresponding to the high reference/feedback set in parameter 6-15 Terminal 53 High Ref./Feedb. Value.
6-14 Terminal 53 Low Ref./Feedb. Value
Default value:
0.000
Setup:
All setups
Data type:
Int32
Enter the reference or feedback value that corresponds to the voltage or current set in parameter 6-10 Terminal 53 Low Voltage to
parameter 6-12 Terminal 53 Low Current.
6-15 Terminal 53 High Ref./Feedb. Value
Default value:
Size related
Setup:
All setups
Data type:
Int32
Enter the reference or feedback value that corresponds to the voltage or current set in parameter 6-11 Terminal 53 High Voltage to
parameter 6-13 Terminal 53 High Current.
6-16 Terminal 53 Filter Time Constant
Default value:
0.01 s
Setup:
All setups
Data type:
Uint16
Enter the time constant. This constant is a first-order digital low-pass filter time constant for suppressing electrical noise in terminal 53. A
high time constant value improves dampening, but also increases the time delay through the filter.
6-19 Terminal 53 mode
Default value:
[1] Voltage mode
Setup:
1 setup
Data type:
Uint8
Select whether terminal 53 is used for current or voltage input.
Option
[0]
[1]
146
| Danfoss A/S © 2024.01
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Name
Current mode
Voltage mode
Range (0.00–20.00 mA)
-2
True
Range (-4999.000–4999.000)
-3
True
Range (-4999.000–4999.000)
-3
True
Range (0.01–10.00 s)
-2
True
Option
–
True
AU275649936274en-001401 / 130R0507