Danfoss VLT AutomationDrive FC 360 Programming Manual page 317

Hide thumbs Also See for VLT AutomationDrive FC 360:
Table of Contents

Advertisement

Programming Guide | VLT® AutomationDrive FC 360
WARNING/ALARM 8, DC Under Voltage
Cause
If the DC-link voltage (DC-link) drops below the under-voltage limit, the drive trips after a fixed time delay. The time delay varies with unit
size.
Troubleshooting
Check that the supply voltage matches the drive voltage.
l
Perform the input voltage test.
l
Perform the soft charge circuit test.
l
WARNING/ALARM 9, Inverter Overload
Cause
The drive is about to cut out because of an overload (too high current for too long). The counter for electronic, thermal inverter
protection issues a warning at 90% and trips at 100%, while giving an alarm. The drive cannot be reset until the counter is below 90%.
The fault occurs when the drive has run with more than 100% overload for too long.
Troubleshooting
Compare the output current shown on the LCP with the drive rated current.
l
Compare the output current shown on the LCP with the measured motor current.
l
Show the thermal drive load on the LCP and monitor the value. When running above the drive continuous current rating, the
l
counter increases. When running below the drive continuous current rating, the counter decreases.
WARNING/ALARM 10, Motor ETR Overtemperature
Cause
According to the electronic thermal protection (ETR), the motor is too hot. Select whether the drive issues a warning or an alarm when
the counter reaches 100% in parameter 1-90 Motor Thermal Protection. The fault occurs when the motor runs with more than 100%
overload for too long.
Troubleshooting
Check for motor overheating.
l
Check if the motor is mechanically overloaded.
l
Check that the motor current set in parameter 1-24 Motor Current is correct.
l
Ensure that the motor data in parameter 1-20 to parameter 1-25 is set correctly.
l
Running AMA in parameter 1-29 Automatic Motor Adaptation (AMA) tunes the drive to the motor more accurately and reduces
l
thermal loading.
WARNING/ALARM 11, Motor Thermistor Overtemperature
Cause
Check whether the thermistor is disconnected. Select whether the drive issues a warning or an alarm in parameter 1-90 Motor Thermal
Protection.
Troubleshooting
Check for motor overheating.
l
Check if the motor is mechanically overloaded.
l
Danfoss A/S © 2024.01
AU275649936274en-001401 / 130R0507 |
315