Programming Guide | VLT® AutomationDrive FC 360
This parameter is not active when parameter 1-10 Motor Construction is set to options that enable PM motor mode.
14-41 AEO Minimum Magnetisation
Default value:
40%
Setup:
All setups
Data type:
Uint8
Enter the minimum allowable magnetization for AEO. Selection of a low value reduces energy loss in the motor, but can also reduce
resistance to sudden load changes.
14-42 Minimum AEO Frequency
Default value:
Size related
Setup:
All setups
Data type:
Uint8
Enter the minimum frequency at which the automatic energy optimization (AEO) is active.
14-44 d-axis current optimization for IPM
Default value:
100%
Setup:
All setups
Data type:
Uint8
This parameter is available only when parameter 1-10 Motor Construction is set to [3] PM, salient IPM. Normally, VVC+ PM control
automatically optimizes d-axis demagnetizing current based on d-axis and q-axis settings. When parameter 1-10 Motor Construction is
set to [3] PM, salient IPM, use this parameter to compensate the saturation effect at high load. Usually, decreasing this value improves
the efficiency. However, 0% means no optimization and the d-axis current is 0 (not recommended).
14-5* Environment
4.13.6
Perform a power cycle after changing any of the parameters in parameter group 14-5* Environment.
These parameters help the drive to operate under special environmental conditions.
14-50 RFI Filter
Default value:
[2] Grid Type
Setup:
1 setup
Data type:
Uint8
Select the RFI filter.
242
| Danfoss A/S © 2024.01
NOTICE
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
NOTICE
Parameter type:
Conversion index:
Change during operation:
Range (10%–100%)
0
True
Range (0–255 Hz)
0
True
Range (0–200%)
0
True
Option
–
False