Programming Guide | VLT® AutomationDrive FC 360
Option
[167]
[168]
[169]
[170]
[171]
[172]
[193]
[194]
5-34 On Delay, Digital Output
Default value:
0.01 s
Setup:
All setups
Data type:
Uint16
Enter the digital output on delay time.
5-35 Off Delay, Digital Output
Default value:
0.01 s
Setup:
All setups
Data type:
Uint16
Enter the digital output off delay time.
Danfoss A/S © 2024.01
Name
Start command active
Drive in hand mode
Drive in auto mode
Homing Completed
Target Position Reached
Position Control Fault
Sleep Mode
Broken Belt Function
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Description
The output is high when the drive is
running counterclockwise (the logical
product of the status bits Running AND
Reverse).
The output is high when the drive is in
hand-on mode.
The output is high when the drive is in
auto-on mode.
The homing operation is completed. This
option is only effective when parameter
37-00 Application Mode is set to [2]
Position Control.
The target position is reached. This option
is only effective when parameter 37-00
Application Mode is set to [2] Position
Control.
A fault occurred in the positioning
process. Refer to parameter 37-18 Pos.
Ctrl Fault Reason for details about the
fault. This option is only effective when
parameter 37-00 Application Mode is set
to [2] Position Control.
The drive/system has entered sleep mode.
See parameter group 22-4* Sleep Mode.
A broken belt condition has been
detected. See parameter group 22-4*
Sleep Mode.
Range (0.00 s–600.00 s)
-2
True
Range (0.00 s–600.00 s)
-2
True
AU275649936274en-001401 / 130R0507 |