Programming Guide | VLT® AutomationDrive FC 360
Enter the X
value manually. Obtain the value from the motor supplier.
l
h
Use the X
default setting. The drive establishes the setting based on the motor nameplate data.
l
h
1-36 Iron Loss Resistance (Rfe)
Default value:
Size related
Setup:
All setups
Data type:
Uint32
Enter the equivalent iron loss resistance value, Rfe. The iron loss resistance value cannot be found by performing an AMA. If Rfe is
unknown, use the default setting for this parameter.
1-37 d-axis Inductance (Ld)
Default value:
Size related
Setup:
All setups
Data type:
Int32
Enter the value of the d-axis inductance. Obtain the value from the permanent magnet motor data sheet or perform an AMA on a cold
motor.
1-38 q-axis Inductance (Lq)
Default value:
Size related
Setup:
All setups
Data type:
Int32
Set the value of the q-axis inductance. Find the value in the motor data sheet or perform an AMA on a cold motor.
1-39 Motor Poles
Default value:
Size related
Setup:
All setups
Data type:
Uint8
Enter the number of motor poles. The motor pole value is always an even number, because it refers to the total pole numbers, not pairs
of poles.
1-4* Adv. Motor Data II
4.2.5
Set parameters for advanced motor data.
1-40 Back EMF at 1000 RPM
Default value:
Size related
Setup:
All setups
Data type:
Uint16
62
| Danfoss A/S © 2024.01
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Range (0.000–2147483.647
Ohm)
-3
False
Range (0.001–65535.000 mH)
-3
False
Range (0.001–65535.000 mH)
-3
False
Range (2–100)
0
False
Range (1–9000 V)
0
False
AU275649936274en-001401 / 130R0507