14-11 Mains Fault Voltage Level
Default value:
342 V
Setup:
All setups
Data type:
Uint16
This parameter defines the threshold voltage at which the selected function in parameter 14-10 Mains Failure is activated. Based on the
supply quality, consider selecting 90% of the nominal mains as the detection level. For a supply of 380 V, parameter 14-11 Mains Fault
Voltage Level should be set to 342 V. This results in a DC detection level of 462 V (parameter 14-11 Mains Fault Voltage Level x 1.35).
14-12 Response to Mains Imbalance
Default value:
[0] Trip
Setup:
1 setup
Data type:
Uint8
Operation under severe mains imbalance conditions reduces the lifetime of the motor. Conditions are considered severe if the motor is
operated continuously near nominal load (for example, a pump or fan running near full speed).
Option
[0]
[1]
[2]
[3]
Danfoss A/S © 2024.01
C
D
t [S]
t [S]
Name
Trip
Warning
Disabled
Derate
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Description
Trip the drive.
Issue a warning.
No action is taken.
Derate the drive.
AU275649936274en-001401 / 130R0507 |
Range (100–800 V)
0
True
Option
True
235