Programming Guide | VLT® AutomationDrive FC 360
Option
[0]
[1]
[2]
[3]
[4]
[11]
[12]
[13]
[14]
1-75 Start Speed [Hz]
Default value:
Size related
Setup:
All setups
Data type:
Uint16
This parameter can be used for hoist applications (cone rotor). Set a motor start speed. After the start signal, the output speed leaps
to the set value. Set the start function in parameter 1-72 Start Function to [3] Start speed cw, [4] Horizontal operation, or [5] VVC+
clockwise, and set a start delay time in parameter 1-71 Start Delay.
1-76 Start Current
Default value:
Size related
Setup:
All setups
Data type:
Uint32
Some motors, for example cone rotor motors, need extra current/starting speed to disengage the rotor. To obtain this boost, set the
required current in this parameter. Set parameter 1-72 Start Function to [3] Start speed cw or [4] Horizontal operation, and set a start
delay time in parameter 1-71 Start Delay.
1-78 Compressor Start Max Speed [Hz]
Default value:
0.0 Hz
72
| Danfoss A/S © 2024.01
Name
Disabled
Enabled
Enabled Always
Enabled Ref. Dir.
Enab. Always Ref. Dir.
v2 Enabled
v2 Enabled Always
v2 Enabled Ref. Dir.
v2 Enab. Alw. Ref. Dir.
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Description
No function.
Enable the drive to catch and control a
spinning motor. When parameter 1-73
Flying Start is enabled, parameter 1-71
Start Delayand parameter 1-72 Start
Function have no function.
Enable flying start at every start
command.
Enable the drive to catch and control a
spinning motor. The search is performed
only in the reference direction.
Enable flying start at every start
command. The search is performed only
in the reference direction.
Enable flying start version 2, after coast.
Enable flying start version 2, at every start.
Enable flying start version 2, after coast,
search in reference direction only.
Enable flying start version 2, ok at every
start, search in reference direction only.
Range (0.0–500.0 Hz)
-1
True
Range (0.00–1000.00 A)
-2
True
Range (0.0–500.0 Hz)
AU275649936274en-001401 / 130R0507