Programming Guide | VLT® AutomationDrive FC 360
Option
[81]
[82]
[83]
[84]
[85]
[86]
[87]
[88]
8-43 PCD Read Configuration
Default value:
Size related
Setup:
1 setup
Data type:
Uint8
Select the parameters to be assigned to the PCDs of the telegrams. The number of available PCDs depends on the telegram type. PCDs
contain the actual data values of the selected parameters.
Enter up to 16 different preset mapping 0-15 in this parameter, using array programming. If this parameter is active, addresses 2910–
2925 represent values of the 16 parameters. If this parameter is not active, addresses 2910 and 2911 are used as status word register and
main actual value. Addresses 2912–2925 are reserved.
Option
[0]
[1]
[2]
[3]
[4]
[5]
[6]
[7]
[8]
[9]
[10]
[11]
[12]
[13]
Danfoss A/S © 2024.01
Name
User Define0
User Define1
User Define2
User Define3
User Define4
User Define5
User Define6
User Define7
Parameter type:
Conversion index:
Change during operation:
Name
None
[1500] Operation Hours
[1501] Running Hours
[1502] kWh Counter
[1600] Control Word
[1601] Reference [Unit]
[1602] Reference %
[1603] Status Word
[1605] Main Actual Value [%]
[1609] Custom Readout
[1610] Power [kW]
[1611] Power [hp]
[1612] Motor Voltage
[1613] Frequency
AU275649936274en-001401 / 130R0507 |
Option, Array [16]
–