To tune the PID controls of the frequency converter, PI-control 0.45 * K 0.833 * P – Danfoss recommends the Ziegler Nichols tuning method. PID tight 0.6 * K 0.5 * P 0.125 * P control NOTICE PID some 0.33 * K...
All Danfoss frequency converters comply with the requirements for the industrial environment and consequently comply also with the lower requirements for home and office environment with a large safety margin.
Using a brake resistor ensures that the heat is absorbed in the brake resistor and not in the Danfoss offers brake resistors with duty cycle of 10% and frequency converter. For more information, see the Brake 40%. If a 10% duty cycle is applied, the brake resistors are Resistor Design Guide.
Page 45
The resistance of the brake resistor should not be higher avoid tripping of the frequency converter. In this situation, than the value recommended by Danfoss. If a brake the ramp-down time is extended. resistor with a higher ohmic value is selected, the 160%...
3.3 Ordering Numbers: Brake Resistors Danfoss offers a wide variety of different resistors that are specially designed to our frequency converters. See chapter 2.9.4 Control with Brake Function for the dimensioning of brake resistors. This section lists the ordering numbers for the brake resistors.
Page 53
3) Measured using 5 m screened motor cables at rated load and rated frequency for enclosure sizes J1–J5, and using 33 m screened motor cables at rated load and rated frequency for enclosure sizes J6 and J7. For energy efficiency class, see the Ambient Conditions section in chapter 4.2 General Specifications. For part load losses, see www.danfoss.com/vltenergyefficiency. MG06B402...
IEC 60364 for CE. protect service personnel and equipment from injuries and damage in case of component breakdown inside the Danfoss recommends using the fuses in Table 4.4 on a frequency converter (first fault). circuit capable of delivering 100000 A (symmetrical), 380–480 V depending on the frequency converter voltage...
NOTICE The FC protocol, also referred to as FC bus or standard The address range depends on the bus, is the Danfoss standard fieldbus. It defines an access protocol selected in 8-30 Protocol. technique according to the master-follower principle for communications via a serial bus.
5.6.1 Prerequisite Knowledge constructs an error message, and send it in response, or a time-out occurs. Danfoss assumes that the installed controller supports the 5.6.3 Frequency Converter with Modbus interfaces in this document, and strictly observes all requirements and limitations stipulated in the controller and frequency converter.
Page 88
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respective companies.