Programming Guide | VLT® AutomationDrive FC 360
Setup:
1 setup
Data type:
Uint16
Set the output frequency transferred to the output terminal 29 when the terminal is configured as [48] Bus Ctrl Timeout in parameter
5-63 Terminal 29 Pulse Output Variable and a timeout is detected.
Parameter Group 6-** Analog In/Out
4.7
Introduction
4.7.1
Parameter group for setting up the analog I/O configuration and the digital output.
The drive provides 2 analog inputs:
Terminal 53
l
Terminal 54
l
The analog inputs can be freely allocated to either voltage (0–10 V) or current input (0/4–20 mA).
6-0* Analog I/O Mode
4.7.2
6-00 Live Zero Timeout Time
Default value:
10 s
Setup:
All setups
Data type:
Uint8
Enter the timeout time.
6-01 Live Zero Timeout Function
Default value:
[0] Off
Setup:
All setups
Data type:
Uint8
Select the timeout function. The function set in parameter 6-01 Live Zero Timeout Function is activated if the input signal on terminal
53 or 54 is below 50% of the value in parameter 6-10 Terminal 53 Low Voltage, parameter 6-12 Terminal 53 Low Current, parameter 6-20
Terminal 54 Low Voltage, or parameter 6-22 Terminal 54 Low Current for a time period defined in parameter 6-00 Live Zero Timeout Time.
Option
[0]
[1]
[2]
[3]
[4]
[5]
144
| Danfoss A/S © 2024.01
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Name
Off
Freeze output
Stop
Jogging
Max. speed
Stop and trip
-2
True
Range (1–99 s)
0
True
Option
True
AU275649936274en-001401 / 130R0507