Programming Guide | VLT® AutomationDrive FC 360
Setup:
All setups
Data type:
Int16
View the torque in percent of nominal torque, with sign, applied to the motor shaft.
16-24 Calibrated Stator Resistance
Default value:
0.0000 Ohm
Setup:
All setups
Data type:
Uint32
Show the calibrated stator resistance.
16-3* Drive Status
4.15.3
16-30 DC Link Voltage
Default value:
0 V
Setup:
1 setup
Data type:
Uint32
View a measured value. The value is filtered with a 128 ms time constant.
16-33 Brake Energy /2 min
Default value:
0.000 kW
Setup:
All setups
Data type:
Uint32
View the brake power sent to an external brake resistor. The average power is calculated on an average level based on the latest 120 s.
16-34 Heatsink Temp.
Default value:
0 °C
Setup:
1 setup
Data type:
Int8
View the drive heat sink temperature. The cutout limit is 90 ±5 °C [194 °F], and the motor cuts back in at 60 ±5 °C [140 °F].
16-35 Inverter Thermal
Default value:
0%
Setup:
1 setup
Data type:
Uint8
View the percentage load on the inverter.
16-36 Inv. Nom. Current
Default value:
0.00 A
Danfoss A/S © 2024.01
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Parameter type:
AU275649936274en-001401 / 130R0507 |
0
False
Range (0.0000–100.0000 Ohm)
-4
True
Range (0–65535 V)
0
True
Range (0.000–10000.000 kW)
-3
False
Range (-128–127 °C)
0
True
Range (0–255%)
0
True
Range (0.00–655.35 A)
257