Programming Guide | VLT® AutomationDrive FC 360
13-41 Logic Rule Operator 1
Default value:
[0] Disabled
Setup:
1 setup
Data type:
Uint8
Select the 1st logical operator to use on the boolean inputs from parameter 13-40 Logic Rule Boolean 1 and parameter 13-42 Logic Rule
Boolean 2.
Option
[0]
[1]
[2]
[3]
[4]
[5]
[6]
[7]
[8]
13-42 Logic Rule Boolean 2
Default value:
[0] False
Setup:
1 setup
Data type:
Uint8
Select the 2nd boolean (true or false) input for the selected logic rule. See parameter 13-01 Start Event ([0]–[61]) and parameter 13-02
Stop Event ([70]– [74]) for further description.
Option
[0]
[1]
220
| Danfoss A/S © 2024.01
Parameter type:
Conversion index:
Change during operation:
Name
Disabled
AND
OR
AND NOT
OR NOT
NOT AND
NOT OR
NOT AND NOT
NOT OR NOT
Parameter type:
Conversion index:
Change during operation:
Name
False
True
Option, Array [6]
–
True
Description
Ignore parameter 13-42 Logic Rule
Boolean 2, parameter 13-43 Logic Rule
Operator 2, and parameter 13-44 Logic
Rule Boolean 3.
Evaluate the expression [13-40] AND
[13-42].
Evaluate the expression [13-40] OR
[13-42].
Evaluate the expression [13-40] AND NOT
[13-42].
Evaluate the expression [13-40] OR NOT
[13-42].
Evaluate the expression NOT [13-40] AND
[13-42].
Evaluate the expression NOT [13-40] OR
[13-42].
Evaluate the expression NOT [13-40] AND
NOT [13-42].
Evaluate the expression NOT [13-40] OR
NOT [13-42].
Option, Array [6]
–
True
AU275649936274en-001401 / 130R0507