B.7 H Parameters: Multi-Function Terminals
u

H6: Pulse Train Input

No.
(Addr.
Name
Hex)
Pulse Train Input
H6-01
Terminal RP Function
(042C)
Selection
H6-02
(042D) Pulse Train Input
Scaling
H6-03
(042E)
Pulse Train Input Gain Term RP Gain
H6-04
(042F)
Pulse Train Input Bias
H6-05
Pulse Train Input Filter
(0430)
Time
H6-08
Pulse Train Input
(043F)
Minimum Frequency
288
LCD Display
0: Frequency reference
Term RP Func Sel
1: PID feedback value
0: Frequency Ref
2: PID setpoint value
1: PID Feedback
5: Flow meter
2: PID Set Point
Note:
5: Flow Meter
Sets the terminal RP input signal frequency that is equal to 100%
of the value selected in H6-01.
Term RP Scaling
Sets the level of the value selected in H6-01 when a frequency
with the value set in H6-02 is input.
Sets the level of the value selected in H6-01 when 0 Hz is input. Default: 0.0%
Term RP Bias
Sets the pulse train input filter time constant.
Term RP Flt Time
Sets the minimum frequency for the pulse train input to be
RP Lower Limit
detected. Enabled when H6-01 = 0, 1, or 2.
Description
When this parameter is set to 5, parameters H6-02
to H6-04 and H6-08 are ignored.
YASKAWA TOEP YAIP1W 01A YASKAWA AC Drive - iQpump1000 Quick Start Guide
Values
Page
Default: 0
Range: 0 to 2; 5
Default: 1440 Hz
Min.: 100
Max.: 32000
Default: 100.0%
Min.: 0.0
Max.: 1000.0
Min.: -100.0
Max.: 100.0
Default: 0.50 s
Min.: 0.00
Max.: 2.00
Default: 0.5 Hz
Min.: 0.1
Max.: 1000.0