SM/SR
SR1002
Ethernet netmask address (32-bit)
SR1003
SR1004
Ethernet gateway address (32-bit)
SR1005
_2
SR1006
Duration of the TCP connection
SR1007
Current Ethernet speed
SR1009
Current TCP connection number
SR1010
Time to restart TCP communication
SR1011
Modbus/TCP Server connection number
SR1012
Modbus/TCP Client connection number
SR1013
EtherNet/IP Adapter connection number
SR1014
EtherNet/IP Scanner connection number
Modbus/TCP Server packet receiving
SR1015
timeout
The delay time for the data to be sent after
SR1016
the connection of Modbus/TCP Client is
established. (ms) (0~1000)
Current AS-FEN02 TCP connection
SR1536
number
AS-FEN02 Modbus/TCP Serves
SR1537
connection number
AS-FEN02 Modbus/TCP Client connection
SR1538
number
AS-FEN02 EtherNet/IP Adapter connection
SR1539
number
 Ethernet communication quality related, available for AS CPU firmware version 1.10.00 or later.
SR
SR1017
SR1018
SR1019
2 - 1 4 0
Function
Function
The maximum number of Ethernet
packets that can be handled in one
scan cycle.
The number of Ethernet packets that
is handled in the last scan cycle.
The accumulated number of Ethernet
packets which are dropped after the
packets in the buffer zone is full.
Action
For example: 255.255.255.0, SR1002 is 16#FFFF, and
SR1003 is FF00
For example: 192.168.1.1, SR1004 is 16#C0A8, and
SR1005 is 0101
Unit: second; default: 30 seconds; setting range: 1-32000; if
the setting value exceeds the setting range, when
When the value exceeds the range, the system treats the
value as the minimum 1 or the maximum 32000.
Unit: Mbps
Number of all the TCP connections
Unit: ms; default: 20 ms; setting range: 0-32000; when the
value exceeds the range, the system treats the value as the
minimum 0 or the maximum 32000. If the setting value is 0,
it indicates system restarts communication automatically.
The system is refreshed automatically.
The system is refreshed automatically.
The system is refreshed automatically.
The system is refreshed automatically.
Unit: ms; default: 10 ms; setting range: 0-32000; when the
value exceeds the range, the system treats the value as the
minimum 0 or the maximum 32000
Unit: ms; default: 10 ms; setting range: 0-1000; when the
value exceeds the range, the system treats the value as the
minimum 0 or the maximum 1000
Number of all AS-FEN02 TCP connections
The system is refreshed automatically.
The system is refreshed automatically.
The system is refreshed automatically.
Action
Default: 80 packets, setting range: 10-1000; when the value
exceeds the range, the system treats the value as the
minimum 10 or the maximum 1000.
Register is refreshed by you.
Refresh the register every scan cycle by the system.
1. Refresh the register every scan cycle by the system.
2. Register can be cleared to 0 by you.