1.
When X0.0=ON, the RST instruction is executed, the current value of C0 is reset to zero, and the output contact of
the counter C0 is FF.
2.
When X0.1 changes from OFF to ON, the value of the counter increments by one.
3.
When the value of the counter C0 reaches the counter setting value of 5, the contact of the counter C0 is ON (the
current value of C0 = the counter setting value = 5). After that the trigger from X0.1 is not accepted by C0 and the
current value of C0 stays at the value 5.
X 0.0
X 0.1
C0 ( PV )
2
1
0
Y 0.0 ,C0
5
4
(SV)
3
0
Cha p ter 2 De vices
2 - 7 7
2_