Chapter 5 Parameters|VFD-B Series
Parameter
Explanation
09-05
Reserved
09-06
Reserved
09-07
Response Delay
Time
Group 10 PID Control Parameters
Parameter
Explanation
Input terminal for
10-00
PID Feedback
Gain over PID
10-01
Detection value
10-02
Proportional Gain (P) 0.0 to 10.0
10-03
Integral Gain (I)
Derivative Control
10-04
(D)
Upper Bound for
10-05
Integral Control
Primary Delay Filter
10-06
Time
PID Output Freq
10-07
Limit
Feedback Signal
10-08
Detection Time
Treatment of the
10-09
Erroneous Feedback
Signals
10-10
PG Pulse Range
10-11
PG Input
ASR (Auto Speed
10-12
Regulation) control
(with PG only) (P)
5-16
Settings
00 ~ 200 msec
Settings
00: Inhibit PID operation
01: Negative PID feedback from external
terminal (AVI) 0 to +10V
02: Negative PID feedback from external
terminal (ACI) 4 to 20mA
03: Positive PID feedback from external
terminal (AVI) 0 to +10V
04: Positive PID feedback from external
terminal (ACI) 4 to 20mA
0.00 to 10.00
0.00 to 100.00 sec (0.00=disable)
0.00 to 1.00 sec
00 to 100%
0.0 to 2.5 sec
0 to 110%
0.0 to 3600.0 sec
00: Warn and keep operation
01: Warn and RAMP to stop
02: Warn and COAST to stop
1 to 40000
00: Disable PG
01: Single phase
02: Forward / Counterclockwise rotation
03: Reverse / Clockwise rotation
0.0 to 10.0
Revision July 2008, BE16, SW V4.08 & V5.00
Factory
Customer
Setting
00
Factory
Customer
Setting
00
1.00
1.0
1.00
0.00
100
0.0
100
60.0
00
600
00
1.0