Appendix 6 Explanation of Alarms

Appendix 6.6 Absolute Position Detection System Alarms (Z7*)

Z70 Abs posn base set incomplete 0001 (Axis name)
Details
Zero point initialization is incomplete. Otherwise, the spindle was removed.
Remedy
Complete zero point initialization.
- Zero point initialization: Required
Z70 Absolute position lost 0002 (Axis name)
Details
The absolute position basic point data saved in the NC has been damaged.
Remedy
Set the parameters. If the basic point data is not
restored by setting the parameters, perform zero point initialization.
- Zero point initialization: (Required)
Z70 Abs posn param changed 0003 (Axis name)
Details
Any of the parameters for absolute position detection has been changed.
#1003 iunit
#1016 iout
#1017 rot
#1018 ccw
#1040 M_inch
#2049 type
Remedy
Correct the parameter settings. Then turn the power
ON again and perform zero point initialization.
- Zero point initialization: Required
Z70 Abs posn initial set illegal 0004 (Axis name)
Details
The zero point initialization point is not at the grid position.
Remedy
Perform the zero point initialization again.
- Zero point initialization: Required
Z70 Abs posn param restored 0005 (Axis name)
Details
The data has been restored by inputting the parameters during the alarm No.0002.
Remedy
Turn the power ON again to start the operation.
- Zero point initialization: Not required
Z70 Abs data error 0006
Details
Deviation of the servo axis with scale when the power is OFF exceeds the set value in "#2051 check
(Check)".
Remedy
Search for the factor which led the deviation of the servo axis at the power OFF.
- Zero point initialization: Not required
- Alarm reset when power is turned OFF: -
- Servo alarm No.: -
IV - 100