Page 1
ANSI power circuit breakers. It may be a part of a single-ended or double- ended load center unit substation. It uses AK/AKJ/AKJT/AKS/AKST Breaker. This manual applies to both Emax 2 Retrofill breakers for AKD-5 switchgear and OEM substructures ...
Features may be described herein that are not present in all hardware and software systems. ABB Inc USA assumes no obligation of notice to holders of this document with respect to changes subsequently made. ABB Inc USA makes no representation or warranty, expressed, implied, or statutory, with respect to, and assumes no responsibility for the accuracy, completeness, sufficiency, or usefulness of the information contained herein.
AKD-5 construction, early 70s. AK25s and AK50s were also available as substructure kits for OEMs to build around customer gear. None of the Emax 2 Retrofill breakers utilize fans except for 3000A rating only. Note: All legacy AK & AKR breakers have a draw out letter code “A”.
Page 9
Note GE Switchboard plants initially shipped “WS” style breakers and later shifted to “WE” style breakers to be consistent with GE Switchgear from Burlington, Iowa. The 5000A breaker had cooling fans. None of the Emax 2 Retrofill breakers utilize fans except the 4000A fully rated breaker.
Page 12
Figure 24 & 25 Fig 24. Rear View of Retrofill Kit Fig 25. Front View of Retrofill Kit The Emax 1.2 & Emax 2.2 Circuit Breaker is suitable for application on power systems up to 600 VAC 50/60 Hz. 2TSA451011P0000 Rev-B...
3. Check the secondary disconnect integrity & mounting supports for any damage or cracks . 4. If switchgear parts show cracks or damage contact ABB post sales service 888-437-3765. 5. Check each breaker compartment for bolted joints in the primary disconnect bars.
Use a lifting device to lift and mount the cassettes and circuit breakers to avoid personal injury or damaging the devices. NOTE: Emax 2 frame 1.2 has no lifting bar. Lift with 2 people to install into cassette. Contact the nearest sales office for availability of a hoisting device or contact ABB post sales service 888-437-3765.
These Emax 2 Retrofill breakers are of two types. AK 25 & 50 circuit breakers are replaced by standard Emax 2 drawout breaker for a Cradle in Cradle (CiC) solution & AKT 50 has a hollow back EntelliGuard R Cradle and uses a customized Emax 2 circuit breaker. The AK 25 &...
Clean and Grease Breaker Before installing or operating a breaker, refer to the Emax 2 Breaker installation manual 1SDH001330R0002 for pre-operation inspecting and testing. Check thoroughly for any damaged or loose parts and for any dirt or foreign matter which may be on the breaker.
Customize retrofill secondary wiring Notice WIRING Before installing the breaker, the secondary disconnects must be wired to the Emax 2 Retrofill Breaker. Wires with wire markers are provided on the Retrofill. Make sure that the switchgear wiring connection points match up with the original wiring of the cubicle.
6. Mount the cassette assembly on the rails of the AKD-5 LVS and rack the cassette into the compartment using the legacy racking system. Note: As the Emax 2 Retrofill breaker is racked into the cassette, and the position indicator window reads “connected” the retrofill Position Switch actuator should activate the compartment mounted position switch in the AKD-5 LVS.
Ensure only qualified personnel install, operate, service and maintain all electrical equipment. Check that the retrofitted Emax 2 cassette has been completely racked into the cabinet. Slide the bracket back into position as shown in the image below (Figure 46) and line up the holes previously drilled with the holes on the locking bracket (figure 47).
Page 35
Peer underneath the breaker, as you maneuver it in, to make sure that the dual blades clear the bottom of cassette (Figure 71). Refer Emax 2 installation manual (1SDH001000R0002) for installing Emax 1.2, 2.2, 4.2 & 6.2 MP (Moving Portion) into the AKD5 compartment.
Note that the circuit breaker is now ready for normal operation 21 - AK/AKT50 Kirkey Interlock The Emax 2.2 Retrofill circuit breakers provided as replacements for AK/AKR circuit breakers have a trip interlock feature which will function using the AKT-50 compartment mounted Key Interlock.
(mounted on the breaker). Figure 78 & 79 shows the AKR disconnects installed on the AK 25 Emax 2 Retrofill cassette. Max up to 4 blocks of secondary disconnects can be installed on AK 25 Emax 2 retrofill cassette (28 points)
Unpack the new door assembly and mount it on the compartment and secure via placing the hinges and tightening the screws. Insert the new retrofitted Emax 2 Retrofill circuit breaker into the compartment and slide the breaker into the disconnected condition. ...
Page 48
Check the through-door racking with the new door assembly. Insert the new retrofitted Emax 2 Retrofill circuit breaker into the compartment and slide the breaker into the disconnected condition. Close the door and secure it to the compartment.
The Neutral CT Adapter supports iron core Neutral sensors compatible with MicroVersa Trip, MVT RMS-9, MVT Plus & PM, Power Plus, Pro Trip & Emax 2 TU rated from 250 to 5000 Amps as used in GE switchboards and switchgear from 1979-2015. It is available in seven variations (shown in Table below).
Refer Relay diagram & 1SDH001000R0524 to identify the terminal marking in circuit diagram. Note: U1 & U2 Emax 2 motor operator (120 V~) terminal. NOTE 1: In the absence of motor or if motor voltage rating is different than 120 V~ , connect 120 V` directly to T1 and T2 ...