Speed Monitoring, Encoder Limit Frequency - Siemens Sinumerik 840D sl Function Manual

Sinumerik safety integrated
Hide thumbs Also See for Sinumerik 840D sl:
Table of Contents

Advertisement

Safety functions integrated in the system/drive
6.5 Safely reduced speed (SG)
Specifying velocities and speeds
The requirements regarding speeds and velocities that are stipulated for individual
processes (milling, turning, grinding, etc.) vary depending on the different C
Standards. For example, the following could be specified for the setting--up mode:
Safely reduced speed with 2 m/min for feed drives and
50 rpm for spindle drives or standstill within 2 revolutions.
The machine manufacturer must parameterize SI in such a way as to ensure full
compliance with the EC Machinery Directive. The relevant standards provide the
necessary guidelines and support.
Quantities that influence the parameterization include, e.g. the drive dynamic
response, the set parameters with their delay times, electrical and mechanical gear
ratios and all of the mechanical properties and characteristics. The interrelation-
ships between the drive dynamic response and internal delay times of SI are
shown in Fig. 6-14 "Timing when exceeding the limit value for SG".
6.5.1

Speed monitoring, encoder limit frequency

When SBH/SG is active in a configuration with a 1--encoder, the speed is moni-
tored to ensure that it does not exceed a maximum encoder limit frequency. An
appropriate alarm is output if this limit is exceeded.
Encoder limit frequency
The encoder limit frequency is 500 kHz. When the encoder limit frequency in SG is
exceeded, the SG--specific parameterized stop is initiated.
Note
Monitoring against a limit frequency of 500 kHz is not performed for DRIVE--CLiQ
encoders.
6-152
SINUMERIK 840D sl/SINAMICS S120 SINUMERIK Safety Integrated (FBSI sl) - - 10.2015 Edition
© Siemens AG 2015 All Rights Reserved
10/15