10/15
A01699 (F)
Response for A:
Acknowledgment
Explanation
Remedy
C01700
Response
Acknowledgment
Explanation
© Siemens AG 2015 All Rights Reserved
SINUMERIK 840D sl/SINAMICS S120 SINUMERIK Safety Integrated (FBSI sl) - - 10.2015 Edition
SI P1 (CU): Shutdown path test required
NONE
NONE
The time set in p9659 for the forced checking procedure of the safety
shutdown paths has been exceeded. The safety shutdown paths must
be re--tested.
After the next time that the "STO" function is deselected, the message
is withdrawn and the monitoring time is reset.
Note:
-- This message does not result in a safety stop response.
-- The test must be performed within the specified maximum time
interval (p9659, maximum 9000 hours) in order to comply with the
specifications in the standard for detecting faults in time and the
conditions to calculate the failure rates of the safety functions
(PFH value).
Operation for longer than this maximum time period is permissible, if it
can be ensured that the forced checking procedure is performed before
persons, who are dependent on the safety functions correctly function-
ing, enter the hazardous area.
See also: p9659 (SI forced checking procedure, timer)
Select STO and then deselect again.
SI Motion P1 (CU): STOP A initiated
OFF2
IMMEDIATELY (POWER ON)
The drive is stopped using a STOP A (the pulses are cancelled via the
safety shutdown path of the Control Unit).
Possible causes:
-- Stop request from the second monitoring channel.
-- STO not active after parameterized time (p9557) after the test stop
was selected.
-- Subsequent response of message C01706: "SI Motion CU: SAM/
SBR limit exceeded".
-- Subsequent response of message C01714 "SI Motion: Safety
limited speed exceeded".
-- Subsequent response of message C01701 "SI Motion: STOP B
initiated".
-- Subsequent response of message C01715 "SI Motion CU: Safely
limited position exceeded".
-- Subsequent response of message C01716 "SI Motion CU:
Tolerance for safe direction of motion exceeded".
10.3Safety messages for SINAMICS S120
Diagnostics
10-767