10/15
p9622[0...1]
SI SBA relay wait times (Control Unit)
Setting the wait times for switching on and switching off the Safe Brake Adapter
relay.
The relay- -specific minimum wait times to evaluate the feedback signal contacts
must be set. For a relay, these differ when switching on and switching off.
[0] = wait time, switching on
[1] = wait time, switching off
See also: p9822
For a crosswise data comparison between p9622 and p9822, a difference of
one safety monitoring clock cycle is tolerated. The parameterized time is
internally rounded- -off to an integer multiple of the monitoring clock cycle.
For index 0:
Wait time switch on = drop- -out time + bounce time NO contact + effect of the
freewheeling diode in the Safe Brake Adapter
For index 1:
Wait time switch off = response time + bounce time NC contact + effect of the
freewheeling diode in the Safe Brake Adapter
Unit:
Default value:
ms
[0] 100
[1] 65
p9625[0...1]
SI HLA shutoff valve wait time (CU)
Sets the wait times for switching on and switching off the shutoff valve.
The valve- -specific minimum wait times to evaluate the feedback signal
contacts must be set.
[0] = wait time, switching on
[1] = wait time, switching off
See also: p9825
Note:
The set time is internally rounded off to an integer multiple of the monitoring
clock cycle (r9780/r9880).
Unit:
Default value:
ms
[0] 250.00
[1] 250.00
p9626[0...1]
SI HLA shutoff valve feedback contacts configuration (CU)
Sets the feedback signal contacts of the shutoff valve to be monitored.
The sensors for the feedback signals of the shutoff valves are connected via
X281/X282.
0: NC contact/NO contact (NC/NO)
1: NC contact / NC contact (NC/NC)
2: NO contact/NO contact (NO/NO)
4: Normally closed contact (NC)
5: Normally open contact (NO)
See also: p9826
Unit:
Default value:
0
© Siemens AG 2015 All Rights Reserved
SINUMERIK 840D sl/SINAMICS S120 SINUMERIK Safety Integrated (FBSI sl) - - 10.2015 Edition
Minimum value:
Maximum value:
0
1000
Minimum value:
Maximum value:
0.00
2000.00
Minimum value:
Maximum value:
0
5
Data Description
8.2 Parameters for SINAMICS S120
Checksum:
Yes
Data type:
Floating Point32
Checksum:
Yes
Data type:
Floating Point32
Checksum:
Yes
Data type:
Integer16
Protection level:
3
Effective:
When exiting the
SI- -commission-
ing mode
Protection level:
3
Effective:
When exiting the
SI- -commission-
ing mode
Protection level:
3
Effective:
When exiting the
SI- -commission-
ing mode
8-461