Warning
!
If two power transistors in the power unit fail at the same time (one in the upper
bridge and one in the lower bridge of the inverter), this can cause brief, limited
movement.
The maximum movement can be:
S Synchronous rotary motors: Maximum motion = 180° / pole pair number
S Synchronous linear motors: Max. movement = pole width
Caution
!
The "automatic restart" function may not be used together with the safety functions
STO/SBC and SS1. The reason for this is that EN 60204--1 Chapter 9.2.5.4.2
does not permit this (merely de--selecting a safety shutdown function must not
cause the machine to restart).
Note
The deactivation all components, e.g. using p0105, with activated Safety functions
is not permitted.