Response for A:
Acknowledgment
Explanation
Remedy
© Siemens AG 2015 All Rights Reserved
SINUMERIK 840D sl/SINAMICS S120 SINUMERIK Safety Integrated (FBSI sl) - - 10.2015 Edition
SI P1 (CU): Write task for parameter rejected
OFF2
IMMEDIATELY (POWER ON)
The write task for one or several Safety Integrated parameters on the
Control Unit (CU) was rejected.
Note:
This fault does not result in a safety stop response.
Fault value (r0949, decimal):
1:
The Safety Integrated password is not set.
2:
A drive parameter reset was selected. However, the Safety Integrated
parameters cannot be reset as Safety Integrated is presently enabled.
3:
The interconnected STO input is in the simulation mode.
10:
An attempt was made to enable the SH (STO) function although this
cannot be supported.
11:
An attempt was made to enable the SBC function although this cannot
be supported.
12:
An attempt was made to enable the SBC function although this cannot
be supported for a parallel circuit configuration.
13:
An attempt was made to enable the SS1 function although this cannot
be supported.
14:
An attempt was made to enable the PROFIsafe communication alt-
hough this cannot be supported.
15:
An attempt was made to enable the motion monitoring functions
integrated in the drive although this cannot be supported.
16:
An attempt was made to enable the SH function although this cannot be
supported when the internal voltage protection (p1231) is enabled.
17:
An attempt was made to enable the PROFisafe function although this
cannot be supported for a parallel circuit configuration.
18:
An attempt was made to enable PROFIsafe for Basic Functions
although this cannot be supported.
19:
An attempt was made to enable SBA (Safe Brake Adapter), although
this cannot be supported.
20:
An attempt was made to enable motion monitoring functions integrated
in the drive and the STO function, both controlled via F--DI
23:
An attempt was made to enable the pulse suppression delay for ESR,
although this cannot be supported.
See also: p0970 (reset infeed parameters), p3900 (complete fast com-
missioning), r9771 (SI common functions (Control Unit)), r9871
(SI common functions (Motor Module))
For fault value = 1:
-- Set the Safety Integrated password (p9761).
For fault value = 2:
-- Inhibit Safety Integrated and again reset the drive parameters.