$MA_SAFE_MODE_SWITCH_TIME
Tolerance time for SGE changeover
Min. input limit: 0.0
Protection level: 7/2
SGE changeover operations do not take effect simultaneously owing to variations in run
times (propagation times) for SGE data transmission in the two monitoring channels.
A crosswise data comparison would, in this case, output an error message.
This data is used to specify the period of time after SGE changeover operations during
which no crosswise comparison of actual values and monitoring results is carried out
(machine data is still compared!). The selected monitoring functions continue to operate
unhindered in both monitoring channels.
A safety- -related function is immediately activated in a monitoring channel if selection or
changeover is detected in this channel.
The different run time (propagation time) is mainly caused by the PLC cycle time.
System- -related minimum tolerance time 2 x PLC cycle time (maximum cycle) + 1 x IPO
cycle time.
The variations in the run times in the external circuitry (e.g. relay operating times) must also
be taken into account.
See Chapter 7.1: "Safety- -relevant input/output signals (SGE/SGA)"
$MA_SAFE_VELO_SWITCH_DELAY
Delay time, speed changeover
Min. input limit: 0.0
Protection level: 7/2
A timer with this value is started when changing from a higher to a lower safely reduced
speed - - or when a safe operating stop is selected when the safely reduced speed function
is active.
While the timer is running, the speed continues to be monitored against the last selected
speed limit value. During this period, the axis/spindle can be braked, for example, from the
PLC user program, without the monitoring function signaling an error and initiating a stop
response.
1. The timer is immediately interrupted as soon as a higher or identical SG limit (i.e. to
that which was previously active) is selected.
2. The timer is immediately interrupted if "non- -safe operation" (SGE "deselect SBH/
SG=1) is selected.
3. The timer is re- -triggered (restarted) if, while the timer is running, a changeover is made
to a lower SG limit than was previously active or to SBH.
Max. input limit: 10.
Unit: s
Max. input limit: 600.
Unit: s