Fan Monitoring; Speed Monitoring With Incremental Encoder; Automatic Restart - Siemens SINAMICS SM150 6SL3815-7NP41-0AA1 Operating Instructions & Installation Instructions

Medium-voltage drive
Table of Contents

Advertisement

Operation
8.5 Functions
8.5.3.5

Fan monitoring

Monitoring the fan ensures that the device functions safely. If the cooling is insufficient, an
alarm is output.
8.5.3.6

Speed monitoring with incremental encoder

Permanent speed monitoring enables motor control without an encoder. You can upgrade with
additional incremental encoders under the following conditions:
● When high-performance applications, such as bearing control, require a permanent speed
● For long-continuing applications with low speeds.
8.5.3.7

Automatic restart

After the power fails and returns, the drive is automatically switched on again, irrespective of
the length of the power failure. Alarms are acknowledged automatically and the drive is
restarted.
Prerequisites
The following general conditions must be satisfied in order that the drive can be switched on:
● The auxiliary supplies must not fail.
● The power supply for the fans, coolant pumps, and the open-loop/closed-loop controllers
If the main infeed fails, the pulse block is initiated. The DC link is supported for a short time using
the precharge.
Starting the drive from standstill
This function is suitable for drives with low moments of inertia and load torques that allow the
drive to come to standstill within seconds, e.g. pump drives with a head of water.
Starting the drive with the "flying restart" function
This function can also be activated as follows: The function is suitable for drives with high inertia
loads (e.g. fan drives). This function can be used to switch the drive to the motor that is still
rotating.
140
control.
must be maintained.
SINAMICS SM150 6SL3815-7NP41-0AA1
Operating Instructions Rev.201910281301 EXAMPLE

Advertisement