Connecting Sensors/Actuators
7.4 Safety- -related CPU- -CPU communication (F_DP communication)
Note
The diagram 7-21 is an example; for I Device, the PN/PN coupler can be
eliminated.
Note
SIMATIC--F--CPUs that support the F_SENDDP/F_RCVDP blocks are suitable as
communication partner, e.g. IM151F.
Note
The chapter only describes the SINUMERIK--specific safety--relevant CPU--CPU
communication to couple plants and systems corresponding to the SIMATIC
F_SENDDP/F_RCVDP protocol specifications. SINUMERIK does not support
SIMATIC S7 communication with F_SENDS7/F_RCVS7.
Description
When configuring F--DP communication between two F--CPUs, an input and output
area must be defined via SIMATIC Step 7 via which the F telegrams are exchan-
ged. The start address (logical basis address) can be freely selected. However,
within an F--CPU it must be the same for the input and output areas. However, a
different start address can be used in the two F--CPUs.
An F--DP communication always comprises a sender (F_SENDDP) and a receiver
(F_RECVDP). Only the sender (in Fig. 7-22 F_SENDDP of the F--CPU1) transfers
F net data -- in the F net data telegram -- to the receiver (in Fig. 7-22 F_RECVDP
of F--CPU2). The receiver only acknowledges the receipt of the F net data tele-
gram using an F acknowledgment telegram. The F acknowledgment telegram does
not contain any F net data.