Diagnostics
10.5 Reducing the number of alarms
10.5
Reducing the number of alarms
In some cases, alarms having the same significance are initiated by the NCK, PLC
and SINAMICS S120 monitoring channels. In order to make the alarm screen
more transparent, the alarms that were initiated sometime later -- but have the
same significance -- are suppressed or even an alarm that occurred earlier is
cleared again if it apparently involves a subsequent (follow--on) fault/error.
Alarm suppression and alarm priority are not involved when it comes to initiating a
stop through two channels. This functionality is implemented independently of the
alarm being initiated and is still maintained.
10.5.1
Alarm suppression
When the alarm suppression function is active, the alarm of the monitoring channel
is displayed that first detected the fault/error that initiated the alarm.
This only applies to some of the alarms. Alarms whose information content differs
depending on the monitoring channels are still separately displayed.
All of the NCK and SINAMICS S120 safety alarms, which can be suppressed with
the appropriate parameterization of $MN_SAFE_ALARM_SUPPRESS_LEVEL,
are shown in the following table.
Table 10-5
NCK alarm
number
27000
27010
27011
27012
27013
27020
27021
27022
27023
27024
All of the NCK alarms are listed in the following table which can be prevented from
being initiated twice due to a PLC request.
10-796
SINUMERIK 840D sl/SINAMICS S120 SINUMERIK Safety Integrated (FBSI sl) - - 10.2015 Edition
Comparison of the NCK and SINAMICS S120 safety alarms
SINAMICS
Alarm suppression using the following values in
S120 alarm
$MN_SAFE_ALARM_SUPPRESS_LEVEL,
number
several values are alternatively possible.
C01797
3, 13, replaced by Alarm 27100
C01707
1, 2, 3, 12, 13
C01714
1, 2, 3, 12, 13
C01715
1, 2, 3, 12, 13
C01706
1, 2, 3, 12, 13
C01710
1, 2, 3, 12, 13
C01709
1, 2, 3, 12, 13
C01708
1, 2, 3, 12, 13
C01701
1, 2, 3, 12, 13
C01700
1, 2, 3, 12, 13
© Siemens AG 2015 All Rights Reserved