Alarm Number:
Possible Cause
Alarm Name
Pn600 (Regenerative
Resistor Capacity) is
not set to 0 and an
External Regenerative
Resistor is not con-
nected to one of the
following SERVO-
PACKs: SGD7S-2R8A
or -2R8F.
The jumper between
the regenerative resis-
tor terminals (B2 and
B3) was removed
from one of the fol-
lowing SERVO-
A.300:
PACKs: SGD7S-
Regeneration
120A.
Error
The External Regener-
ative Resistor is not
wired correctly, or was
removed or discon-
nected.
A failure occurred in
the SERVOPACK.
3.5 FT83 SERVOPACKs with Analog Voltage/Pulse Train References
Confirmation
Connect an External
Check it see if an Exter-
Regenerative Resistor, or
nal Regenerative Resis-
set Pn600 (Regenerative
tor is connected and
Resistor Capacity) to 0
(setting unit: ×10 W) if no
check the setting of
Pn600.
Regenerative Resistor is
required.
Check to see if the
jumper is connected
Correctly connect a
between power supply
jumper.
terminals.
Check the wiring of the
Correct the wiring of the
External Regenerative
External Regenerative
Resistor.
Resistor.
While the main circuit
power supply is OFF, turn
the control power supply
to the SERVOPACK OFF
and ON again. If an alarm
still occurs, the SERVO-
PACK may be faulty.
Replace the SERVO-
PACK.
3.5.3 Troubleshooting Alarms
Continued from previous page.
Correction
Reference
*1
*1
Continued on next page.
3
3-215