YASKAWA SGM7D-30F Product Manual page 256

E-7-series ac servo drive e-7s servopack with ft/ex specification for application with special motor, sgm7d motor
Table of Contents

Advertisement

Warning Number:
Possible Cause
Warning Name
The surrounding
temperature is too
high.
Operation was
performed under
an excessive load.
A.93B:
Overheat Warning
A failure occurred
in the SERVO-
PACK.
The sensor
attached to the
machine is faulty.
The speed ripple
compensation
information stored
A.942:
in the encoder
Speed Ripple Com-
does not agree
pensation Informa-
with the speed
ripple compensa-
tion Disagreement
tion information
stored in the SER-
VOPACK.
For a 200-V SER-
VOPACK, the AC
power supply volt-
age dropped
below 140 V.
For a 100-V SER-
VOPACK, the AC
power supply volt-
age dropped
below 60 V.
The power supply
A.971:
voltage dropped
Undervoltage
during operation.
A momentary
power interrup-
tion occurred.
The SERVOPACK
fuse is blown out.
A failure occurred
in the SERVO-
PACK.
3.4 Command Option Attachable-type FT82 SERVOPACKs with INDEXER Modules
Confirmation
Check the surrounding
temperature using a
thermostat.
Use the accumulated
load ratio to check the
load during operation.
Measure the power
supply voltage.
Measure the power
supply voltage.
Measure the power
supply voltage.
Measure the power
supply voltage.
3.4.7 Troubleshooting Warnings
Continued from previous page.
Correction
Lower the surrounding tem-
perature by improving the
installation conditions of the
machine.
Reconsider the load and
operating conditions.
The SERVOPACK may be
faulty. Replace the SERVO-
PACK.
The sensor attached to the
machine may be faulty.
Repair the sensor attached
to the machine.
Reset the speed ripple
compensation value on the
SigmaWin+.
Set Pn423 to n.1 (Do
not detect A.942 alarms).
However, changing the set-
ting may increase the speed
ripple.
Set Pn423 to n.0
(Disable torque ripple com-
pensation). However,
changing the setting may
increase the speed ripple.
Set the power supply volt-
age within the specified
range.
Set the power supply volt-
age within the specified
range.
Increase the power supply
capacity.
If you have changed the
setting of Pn509 (Momen-
tary Power Interruption Hold
Time), decrease the setting.
Replace the SERVOPACK
and connect a reactor.
The SERVOPACK may be
faulty. Replace the SERVO-
PACK.
Continued on next page.
Reference
*
*
*
*
*
3
3-187