YASKAWA SGD7C-***AMAA*** Product Manual page 285

Ac servo drive
Table of Contents

Advertisement

5.28 Forcing the Motor to Stop
5.28.2 Stopping Method Selection for Forced Stops
Stopping the Servomotor by Setting Emergency Stop
Torque (Pn406)
To stop the Servomotor by setting emergency stop torque, set Pn406 (Emergency Stop
Torque).
If Pn001 = n.
torque set in Pn406 as the maximum torque.
The default setting is 800%. This setting is large enough to allow you to operate the Servomo-
tor at the maximum torque. However, the maximum emergency stop torque that you can actu-
ally use is the maximum torque of the Servomotor.
Pn406
*
Set a percentage of the rated motor torque.
Stopping the Servomotor by Setting the Deceleration Time
for Servo OFF and Forced Stops (Pn30A)
To specify the Servomotor deceleration time and use it to stop the Servomotor, set Pn30A
(Deceleration Time for Servo OFF and Forced Stops).
Pn30A
If you set Pn30A to 0, the Servomotor will be stopped with a zero speed.
The deceleration time that you set in Pn30A is the time to decelerate the Servomotor from the
maximum motor speed.
Maximum peed
Operating peed
5-88

X
is set to 1 or 2, the Servomotor will be decelerated to a stop using the
Emergency Stop Torque
Setting Range
Setting Unit
0 to 800
Deceleration Time for Servo OFF and Forced Stops
Setting Range
Setting Unit
0 to 10,000
Default Setting
1%*
800
Default Setting
1 ms
0
Actual deceleration time =
Actual
deceleration
time
Pn 0A
peed
Po ition
When Enabled
Immediately
peed
Po ition
When Enabled
Immediately
Operating peed
× Deceleration time (Pn 0A)
Maximum peed
Torque
Classifica-
tion
Setup
Classifica-
tion
Setup

Advertisement

Table of Contents
loading

Table of Contents