5.19 I/O Signal Allocations
5.19.10 Speed Limit during Torque Control
Selecting the Speed Limit
The smaller of the external speed limit and internal speed limit will be used.
 Internal Speed Limiting
Set the speed limit for the motor in Pn407 (Speed Limit during Torque Control) or Pn480
(Speed Limit during Force Control).
Also set Pn408 = n.
or the overspeed alarm detection speed as the speed limit. Select the overspeed alarm detec-
tion speed to limit the speed to the equivalent of the maximum motor speed.
Pn408
Note: If you are using a Rotary Servomotor, set Pn407 (Speed Limit during Torque Control). If you are using a Linear
Servomotor, set Pn480 (Speed Limit during Force Control).
• Rotary Servomotors
Pn407
• Linear Servomotors
Pn480
Note: If the parameter setting exceeds the maximum speed of the Servomotor, the Servomotor's maximum speed
or the overspeed alarm detection speed will be used.
 External Speed Limiting
The motor speed will be limited by OW0E (Speed Limit for Torque/Force Reference).
Refer to the following manual for details.
Σ-7-Series Σ-7C SERVOPACK Motion Control User's Manual (Manual No.: SIEP S800002 03)
5-64

X
(Speed Limit Selection) to specify using the maximum motor speed
Parameter
Use the smaller of the maximum motor

n.
0
speed and the setting of Pn407 or Pn480 as
(default setting)
the speed limit.
Use the smaller of the overspeed alarm

n.
1
detection speed and the setting of Pn407 or
Pn480 as the speed limit.
Speed Limit during Torque Control
Setting Range
0 to 10,000
Speed Limit during Force Control
Setting Range
Setting Unit
0 to 10,000
Meaning
Setting Unit
Default Setting
-1
10000
1 min
Default Setting
1 mm/s
10000
When Enabled
Classification
After restart
Setup
Torque
When Enabled
Classification
Immediately
Setup
Force
When Enabled
Classification
Immediately
Setup