5.11 Overtravel Function and Settings
5.11.3 Motor Stopping Method for Overtravel
Stopping the Servomotor by Setting Emergency Stop
Torque
To stop the Servomotor by setting emergency stop torque, set Pn406 (Emergency Stop
Torque).
If Pn001 = n.
torque set in Pn406 as the maximum torque.
The default setting is 800%. This setting is large enough to allow you to operate the Servomo-
tor at the maximum torque. However, the maximum emergency stop torque that you can actu-
ally use is the maximum torque of the Servomotor.
Pn406
*
Set a percentage of the motor rated torque.
Stopping the Servomotor by Setting the Deceleration Time
To specify the Servomotor deceleration time and use it to stop the Servomotor, set Pn30A
(Deceleration Time for Servo OFF and Forced Stops).
Pn30A
If you set Pn30A to 0, the Servomotor will be stopped with a zero speed.
The deceleration time that you set in Pn30A is the time to decelerate the Servomotor from the
maximum motor speed.
Maximum peed
Operating peed
5-30

X
is set to 1 or 2, the Servomotor will be decelerated to a stop using the
Emergency Stop Torque
Setting Range
Setting Unit
0 to 800
Deceleration Time for Servo OFF and Forced Stops
Setting Range
Setting Unit
0 to 10,000
Default Setting
1%*
800
Default Setting
1 ms
0
Actual deceleration time =
Actual
deceleration
time
Pn 0A
peed
Po ition
When Enabled
Classification
Immediately
peed
Po ition
When Enabled
Classification
Immediately
Operating peed
× Deceleration time (Pn 0A)
Maximum peed
Torque
Setup
Setup