WAGO-I/O-SYSTEM 750
750-531 4DO 24V DC 0.5A/ 2-conductor
Table 13: Technical Data – Power Jumper Contacts
Power jumper contacts
Voltage drop at I
Pos : 46.4 /Serie 750 (WAGO-I/O-SYST EM)/Ger ätebesc hrei bung/T echnisc he Daten/Ansc hluss tec hni k/T ec hnisc he D aten Datenkontakte @ 17\mod_1380123495844_21.doc x @ 132794 @ @ 1
Table 14: Technical Data – Data Contacts
Data contacts
Pos : 47 /Serie 750 ( WAGO-I/O-SYST EM)/Ger ätebesc hrei bung/T echnisc he Daten/Kli matische U mweltbeding ung en/Technisc he Daten Klimat. U mweltbed. ohne erw. T emp. 0...55°C /-25...+85°C @ 5\mod_1247657968368_21.doc x @ 37603 @ 3 @ 1
3.6.6

Climatic Environmental Conditions

Table 15: Technical Data – Climatic Environmental Conditions
Operating temperature range
Storage temperature range
Relative humidity without condensation Max. 95 %
Resistance to harmful substances
Maximum pollutant concentration at
relative humidity < 75 %
Special conditions
Pos : 48 /D okumentation allgemei n/Glieder ungs elemente/---Seitenwechs el--- @ 3\mod_1221108045078_0.doc x @ 21810 @ @ 1
Manual
Version 1.3.0
max.
Device Description
Blade/spring contact, self-cleaning
< 1 V/64 modules
Slide contact, hard gold plated, self-
cleaning
0 °C ... 55 °C
−25 °C ... +85 °C
Acc. to IEC 60068-2-42 and
IEC 60068-2-43
SO
≤ 25 ppm
2
H
S ≤ 10 ppm
2
Ensure that additional measures for
components are taken, which are used in
an environment involving:
– dust, caustic vapors or gases
– ionizing radiation
23